| Alternative NSN: 5920-01-447-0784 |
| Item Name: Protector Series Ci |
| CAGE Code : 59138 , 0CAT4 |
| NIIN: 014470784 |
| FSC Name: 5920 Fuses Arresters Absorbers and Protector |
| NCB Code: USA (01) |
| Manufacturers: instrument transformers inc , point eight power inc |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| OCPC-200-P | instrument transformers inc | protector series ci | Avl | |
| 1-OCP-200 | instrument transformers inc | protector series ci | Avl | |
| 3831-7 MK 65 | point eight power inc | protector series ci | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| ABHP | Overall Length | 5.000 INCHES NOMINAL |
| ABMK | Overall Width | 3.700 INCHES NOMINAL |
| FTLD | Functional Description | USED FOR OPEN CIRCUIT PROTECTION FOR RELAY CLASSES C100 THRU C200 |
| TEXT | General Characteristics Item Description | JONE ELEMENT, RELAY CLASS PROTECTION C100 THRU C200; FREQUENCY 50 TO 400 HZ; AMBIENT TEMP RANCE -30 DEG C TO +55 DEG C; NORMAL SECONDARY CURRENT 5 AMPS AC; SHORT TIME OVERCURRENT 100 AMPS FOR 2 SECONDS; MAX CONTINUOUS CURRENT 10 AMPS THROUGH ONE ELEMENT OR 7.5 AMPS THROUGH ALL THREE INDEPENDENT ELEMENT; COPPER TERMINALS WITH BRASS SLOTTED PAN HEAD SCREWS NO. 8-32 X 1/4 WITH CUPPED WASHERS; WEIGHT 1.2 LBS; STANDARD BURDEN 2 OHMS; CLAMPING PEAK VOLTAGE LIMIT 400 V |
| CXCY | Part Name Assigned By Controlling Agency | OPEN CIRCUIT PROTECTOR |
| MRC | Decoded Requirement | Clear Text Reply |
| ABKW | Overall Height | 2.000 INCHES NOMINAL |