| Alternative NSN: 5925-00-080-1019 |
| Item Name: Circuit Breaker |
| CAGE Code : 88360 , 56365 , 52090 , 79405 |
| NIIN: 000801019 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: international business machines corp , schneider electric gmbh , telemecanique inc , wood electric operations potter and brumfield |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| 524179 | international business machines corp | circuit breaker | Avl | |
| CCPBA18 | schneider electric gmbh | circuit breaker | Avl | |
| CCPBA18 | telemecanique inc | circuit breaker | Avl | |
| 114-208-103 | wood electric operations potter and brumfield | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ABHP | OVERALL LENGTH | 1.969 INCHES NOMINAL |
| ABMK | OVERALL WIDTH | 0.997 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.656 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.000 INCHES NOMINAL |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE,DOUBLE THROW |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.120 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.910 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | AIR |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 8.0 AMPERES AC AND 8.0 AMPERES DC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 230.0 AC AND 20.0 DC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 200.0 AC AND 200.0 DC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 23.000 MINIMUM AT 200 PCT AND 23.000 MAXIMUM AT 300 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 24.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
| CRTK | SWITCH TERMINAL TYPE | PIN |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 3.0 AC AND 3.0 DC |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 115.0 AC AND 50.0 DC |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |
Before You Go, You Should Consider Looking at Our NSN Parts Catalog. and Remember, ASAP Sourcing Solutions Has Some of the Fastest and Most Competitive Quotes On the Market.
Request for Quote