Alternative NSN: 5925-00-135-4265 |
Item Name: Circuit Breaker |
CAGE Code : 66842 , 60555 , 30086 |
NIIN: 001354265 |
FSC Name: 5925 Circuit Breakers |
NCB Code: USA (00) |
Manufacturers: siemens energy and automation inc , siemensallis inc , spd electrical systems inc |
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
---|---|---|---|---|
CJ3-M225 | siemens energy and automation inc | circuit breaker | Avl | |
CLF63M225 | siemens energy and automation inc | circuit breaker | Avl | |
CFD63M225 | siemens energy and automation inc | circuit breaker | Avl | |
CJ3M225 | siemensallis inc | circuit breaker | Avl | |
CJ3-M225 | spd electrical systems inc | circuit breaker | Avl |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 11.938 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.500 INCHES NOMINAL |
ADAU | BODY HEIGHT | 4.062 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 10.688 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.188 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 225.0 AMPERES AC AND 225.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 100000.0 AC AND 100000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQJX | NOMINAL THREAD SIZE | 0.164 INCHES |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
Before You Go, You Should Consider Looking at Our NSN Parts Catalog. and Remember, ASAP Sourcing Solutions Has Some of the Fastest and Most Competitive Quotes On the Market.
Request for Quote