| Alternative NSN: 5925-00-733-4565 |
| Item Name: Circuit Breaker |
| CAGE Code : 32856 , 21810 , 053Q1 |
| NIIN: 007334565 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: american circuit breaker corp , challenger electrical equipment corp , federal pacific electric co |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| XM433600 | american circuit breaker corp | circuit breaker | Avl | |
| XM633600 | challenger electrical equipment corp | circuit breaker | Avl | |
| XM433600 | challenger electrical equipment corp | circuit breaker | Avl | |
| XM631600 | challenger electrical equipment corp | circuit breaker | Avl | |
| XM433600 | federal pacific electric co | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| ABMK | OVERALL WIDTH | 8.250 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 100000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CTJS | UNPACKAGED UNIT WEIGHT | 58.000 POUNDS NOMINAL |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| ABHP | OVERALL LENGTH | 24.523 INCHES NOMINAL |
| ABKW | OVERALL HEIGHT | 5.420 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND CURRENT LIMITER |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 600.0 AMPERES AC ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 3000.0 TO 6000.0 AC ALL LOCATIONS |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT AND 32.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |