| Alternative NSN: 5925-00-782-6845 |
| Item Name: Circuit Breaker |
| CAGE Code : 81348 , 56365 |
| NIIN: 007826845 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: federal specifications , schneider electric gmbh |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| W-C-375 1 | federal specifications | circuit breaker | Avl | |
| WC375 01 011 | federal specifications | circuit breaker | Avl | |
| Q0170 | schneider electric gmbh | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAT | BODY WIDTH | 0.720 INCHES MINIMUM AND 0.740 INCHES MAXIMUM |
| AJEC | BOSS HEIGHT | 0.240 INCHES MINIMUM AND 0.260 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| TTQY | TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 COMPRESSION |
| ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/1 GOVERNMENT SPECIFICATION |
| ADAQ | BODY LENGTH | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
| ADAU | BODY HEIGHT | 2.570 INCHES MINIMUM AND 2.590 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 120.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| TEST | TEST DATA DOCUMENT | 81348-W-C-375 SPECIFICATION INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTING G |
Before You Go, You Should Consider Looking at Our NSN Parts Catalog. and Remember, ASAP Sourcing Solutions Has Some of the Fastest and Most Competitive Quotes On the Market.