| Alternative NSN: 5925-00-856-3629 |
| Item Name: Circuit Breaker |
| CAGE Code : 21810 |
| NIIN: 008563629 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: challenger electrical equipment corp |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| NE111030 | challenger electrical equipment corp | circuit breaker | Avl | |
| NEF213030 | challenger electrical equipment corp | circuit breaker | Avl | |
| NEF212030 | challenger electrical equipment corp | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| ABTD | MOUNTING SLOT WIDTH | 0.375 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 6.219 INCHES NOMINAL |
| ADAT | BODY WIDTH | 1.375 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.219 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.125 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.203 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 1 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 SLOT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC AND 30.0 AMPERES DC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 12.000 MINIMUM AT 200 PCT AND 35.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CWJK | CASE MATERIAL | PLASTIC |
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAU | BODY HEIGHT | 3.406 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.000 INCHES NOMINAL |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC AND 125.0 DC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 14000.0 AC AND 10000.0 DC SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 COMPRESSION |
Before You Go, You Should Consider Looking at Our NSN Parts Catalog. and Remember, ASAP Sourcing Solutions Has Some of the Fastest and Most Competitive Quotes On the Market.
Request for Quote