| Alternative NSN: 5925-01-327-5458 |
| Item Name: Circuit Breaker |
| CAGE Code : 20227 , 81511 , 81541 |
| NIIN: 013275458 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (01) |
| Manufacturers: henley marine inc , perkin-elmer corp , sensata technologies inc |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| 28075310 | henley marine inc | circuit breaker | Avl | |
| IEL11124943-1-V | perkin-elmer corp | circuit breaker | Avl | |
| IEL111-24943-1-V | sensata technologies inc | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC SECOND LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.180 MINIMUM AT 200 PCT AND 1.800 MAXIMUM AT 200 PCT ALL LOCATIONS |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND MOISTURE RESISTANT AND SHOCKPROOF AND VIBRATIONPROOF AND FUNGUS RESISTANT |
| CTJS | UNPACKAGED UNIT WEIGHT | 11.100 OUNCES NOMINAL |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES MAXIMUM |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC FIRST LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| ADAQ | BODY LENGTH | 2.490 INCHES NOMINAL |
| ADAT | BODY WIDTH | 2.265 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC THIRD LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |