| CM-21A | 3m company | alarm gas automatic | Avl | |
| CM-21A | aerion technologies inc | alarm gas automatic | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
| AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
| SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
| FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
| BRQN | MEDIA DETECTED | CARBON MONOXIDE |
| CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
| ALBY | USAGE DESIGN | INDUSTRIAL |
| ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
| AMKD | INDICATOR TYPE | RED LIGHT AND HORN |